![]() |
||||||||||||||
www.espresso-restorations.com The Espresso Machine Restoration site A non-commercial site for those interested in espresso equipment repair and restoration. |
![]() |
|||||||||||||
From the workbench 2 |
![]() |
|||||||||||||
Component Checklist |
||||||||||||||
Procon Pump Ideal pressure is around 9 bar 9 bar is 135psi |
Troubleshooting Very noisy - There may be some air in the water line or the mains water supply is off. Check the mains supply. Not pumping - Assuming that the motor is OK, the pump may have some debris or object blocking it. Try and turn by hand and/or descale. Also make the sure that if it has a check valve, it is not blocked. If it turns and still not pumping then you need to replace. Pressure adjustment - Turn the acorn screw clockwise to increase and anticlockwise to decrease. Can it be rebuilt? Yes only at the factory though. Do not attempt to do it yourself! |
|||||||||||||
Motor and Capacitor Capacitors measured in uf Replace with the same uf capacitor |
Troubleshooting Motor not turning (1) - Ensure the electrical connections are good. If so check that the capacitor is OK by checking the ohms. Set multimeter on the highest ohms setting then connect the leads to the 2 terminals on the capacitor. The display value should rapidly decrease then increase after it reaches zero. If you reverse the leads (swap polarity) and the same readout occurs then the capacitor is ok. Motor not turning (2) - It has been known that a screw or similar object can block the motor from turning. Also check that the fan casing at the back is aligned - if the cooling fins are blocked that will stop the motor from turning. Motor starts slowly - Replace the start capacitor. |
|||||||||||||
Solenoids Test coil. 0.7kohms - 0.8kohms |
Troubleshooting Lack of flow from group head (1) - If water supplu and flowmeters are ok, the 3 way valve is blocked. Clean with a detergent such as Puly Caff. Lack of flow from group head (2) - Valve coil is dead. Check ohm reading of the coil. 0.7-0.8k ohms is a good coil. Water dripping from group head or into drain - The plunger (piston) gasket and spring may be worn. Replace the plunger and spring. Filling of boiler has a problem - Slow flow would indicate scale build-up inside valve - descale. No flow may indicate a severe blockage or dead coil. Contantly filling (coil not energised) may indicate plunger is worn. |
|||||||||||||
Flowmeter Test field sensor. 1.8kohms -2.4kohms |
Troubleshooting Lack of flow to group head - Check the inlet hole is not blocked. It is very small. Blocked flowmeter - Take apart, clean and descale. Water leaking from flowmeter - Check pipe fittings and tighten if necessary. If leaking from the main body replace the o-ring. Computer says no flow - Check mains water supply and group 3 way valve for operation. If ok check the field sensor on the flowmeter. Ohms reading between the "+" and "0" terminal should be 2.2k. Check also that the magnets are ok. |
|||||||||||||
Pressure Switch Deadband of 0.5 bar max. Check continuity between Common and NC |
Troubleshooting Safety Valve blowing at 1.8bar - Adjust the p-stat downwards. If it continues check the membrane (on a Sirai) and replace if it is stiff. If after adjusting the p-stat downwards the deadband is too large replace the p-stat (CEME or MATER) or the membrane on a Sirai. No power to heating elements (1) - Check the high temp safety fuse and push the red button back in. This is an indication that your p-stat is on it's way out and needs replacement. No power to heating elements (2) - Check the relay or contactor switch for operation. |
|||||||||||||
Contactors Check the switch to see if it closes during operation. Clean contacts. |
Troubleshooting No power to heating elements - Check that the switch is working. Check that the coil is OK and that the switch is closing when energised. If the contacts are clean and ok then check the power leads for the elements and then the safety pop fuse. Make certain the contactor can handle the power of the element. Make certain the contactor is of the correct voltage. i.e. A1 and A2 input is the correct 110V or 220V. |
|||||||||||||
Solid State Relay Add a heatsink. Mount in a cool place. |
Troubleshooting No power to heating elements - If the voltage accross the load terminal is OK then check the switching voltage. If it is OK the SSR is not good. It may have overheated. remember that an SSR is useless without a good heatsink and the rating is dramatically reduced without a heatsink. Use an appropriate heatsink and heat transfer compound. Make sure the input is what you need, i.e. AC or DC, Make the sure the rating is suitable. |
|||||||||||||
Heating elements Ensure correct voltage Check wiring and safety fuses. |
Troubleshooting Water not heating - Check that the elements are receiving a current. If not it could be the pressure switch or the thermostat. Check the wiring. Water heating very slowly - Check that the elements are the correct wattage for that size boiler. Check for limescale build up on the elements. If no scale then replace the elements. |
|||||||||||||
Steam valves Replace gasket/washer frequently. Use a silicone lubricant. |
Troubleshooting Valve does not close properly and steam leaks from the tip - You must replace the gaskets inside the valve, usually the end stopper gasket. It could also be the spring inside that is not returning the valve back into position. It could also be that inside the valve there is no lubricant - you should use a silicone lubricant. Valve will not open - May be stuck with scale or dirt. No steam - Valve tip is blocked with milk. Clean the holes with a paper-clip. If boiler is hot and tip is free of milk then the blockage is further up. It may be scale or dirt. |
|||||||||||||
This website is created by Paul Pratt, Hong Kong 2004. If you would like to use any of the images or text I am sure I will say yes, but please ask first! Email me here. |